Micro Motion 2700 Transmitter = Flashing Red (Zero reading at flow conditions/ Erratic flow rate at no-flow conditions)

Status LED

Figure 1.1 - Flashing Red (Erratic flow rate)


#Observed the Status LED
Flashing RED = One or more high-severity alerts are active and have not been acknowledged.
Figure 1.2 - Flashing Red (Zero reading)

1). Check the wiring between the Sensor and the Transmitter.
→Faulty cable, improper wire termination, or loose wires or connectors.
→Shorts to the housing created by trapped or damaged wires.
2). Inspect the Sensor and Core Processor
→For sensors with a junction box, check for moisture inside the junction box (Ensure that the junction box is dry and no corrosion is present).
Figure 1.3 - Core Processor (TH050 Sensor)

#Possible Cause
→Moisture inside the sensor junction box (short circuit).
→Liquid or moisture inside the sensor case (intermittent signal).
→Sensor/Core Processor damage.
Figure 1.4 - Water/Moisture Ingress 

#Recommended Action
→Dry completely with clean compressed air, and clean corrosion on terminals with contact cleaner/electrical cleaner.
→Check gasket and o-ring on the housing cover. Replace if hardener or torn.
→Check cable glands at the bottom (most common entry point for water).
→Reseal with silicone grease on the gasket before closing.
→Replace the Core Processor.

3). Replace the Sensor Assembly (TH050/ Model 800)
→Disconnect the wires to the Core Processor.
→Remove the piping and the sensor assembly.
→Replace the corroded bolts.
→Mount the Sensor (Flow direction arrow on the sensor case matches the actual forward flow of the process).
Figure 1.5 - Model 800 (Enhanced Core Processor)
→Connect the wires to the Core Processor.
A = Terminal 1 (Power Supply +)
B = Terminal 2 (Power Supply -)
C = Terminal 3 (RS-485/A)
D = Terminal 4 (RS-485/B)

4). Connect with ProLink III
→Check the Calibration Factors (Refer to the Name Plate) = Device Tools - Calibration Data.
Figure 1.6 - Flow Calibration Factor
→Flow Calibration Factor (FCF, FT) and Density Calibration Factors (D1, D2, DT, K1, K2, FD, FTG, FFQ, DTG, DFQ1, DFQ2).

5). After Replace the Sensor Assembly
Figure 1.7 - Flashing Green