1.8004.568 (Alarm No.214/ SD P-CrankCase) - Crankcase Pressure Sensor Defect, Short Circuit or Cable Breakage (MTU 12V4000S83L)
SD P-CrankCase
![]() |
| Figure 1.1 - SS P-Crank Case (SAM) |
1). Connecting to the system in the SAM diagnostic connector (X4), with Ixxat USB-to-CAN v2 and DiaSys software.
2). On the Available Functions menu, click on the Logfiles...
3). Open Error logfile button
![]() |
| Figure 1.3 - Error logfile |
![]() |
| Figure 1.5 - Module upload |
→Short circuit or cable breakage
5). Check Sensor and Cable (B50), if necessary replace it.
→Measuring the sensor voltage (5Vdc/OK), and Pull-up voltage (13Vdc/OK)
Read More:
6). Delete Error Logfile
→Deletes the error messages stored in the governor.
→Back to Logfiles menu (refer to Figure 1.3 above), then open Delete error logfile
![]() |
| Figure 2.1 - Delete error logfile (Offline) |